Table 1. Output Module Offline Fault Troubleshooting Procedures -- Continued
Table 1. Output Module Offline Fault Troubleshooting Procedures -- Continued

Field Maintenance Manual For Bituminous Material Paving Machine - 1 Page Navigation
  738    739    740    741    742  743  744    745    746    747    748  
img
TM 5-3895-385-23-1
0182
Table 1. Output Module Offline Fault Troubleshooting Procedures -- Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
2. If no continuity is present,
proceed to next test.
3. Measure continuity (WP 0443,
1. If continuity is present, replace
Vol 3) from C1 J1 pin C to every
damaged communication cable
other pin on C1 J1 (WP 0451,
(WP 0386, Vol 2).
Vol 3, Figure 51).
2. If no continuity is present,
proceed to next malfunction.
9. Communication cable C9
Check communication cable C9 J1
1. If damage is found, replace
disconnected.
and J2 for proper connection and
communication cable C9 (WP
damage (WP 0451, Vol 3, Figure
0386, Vol 2).
51).
2. If communication cable is found
disconnected, reconnect
communication cable properly.
3. If no damage or loose
connection is found, proceed to
next malfunction.
10. Communication cable C9 has
1. Disconnect communication cable
an open circuit.
C9 J1 from Y6 P1 (WP 0451, Vol
3, Figure 51).
2. Disconnect communication cable
C9 J2 from Y7 P1 (WP 0451, Vol
3, Figure 51).
3. Measure for continuity (WP
1. If continuity is present, proceed
0443, Vol 3) from C9 J1 pin A to
to next test.
C9 J2 pin A (WP 0451, Vol 3,
Figure 51).
2. If no continuity is present,
replace damaged
communication cable (WP 0386,
Vol 2).
4. Measure for continuity (WP
1. If continuity is present, proceed
0443, Vol 3) from C9 J1 pin B to
to next test.
C9 J2 pin B (WP 0451, Vol 3,
Figure 51).
0182-6